The LCR-1 load control interface relay is designed to allow interconnection of utility load management receivers and customer-owned equipment involved in a load management program. The LCR-1's 2-wire input provides a +24VDC sense (wetting) voltage source which is switched by the load management receiver or other sending device, and returned to the LCR-1. When the +24VDC voltage is sensed, the LCR-1's relay is energized closing the normally-open contacts and opening the normally-closed contacts. The LCR-1 contains a 3-Wire Form "C" output (Common, Normally Open, & Normally Closed) capable of switching up to 3 Amps.
| Power Input | 90 to 135 VAC or 180 to 300VAC. Burden: 10 MA. at 120 VAC |
| Output | One "dry" form "C" contact (COM, NO, & NC). The contacts are rated at 28 VDC or 250 VAC @ 3 Amps. Factory fused at 2 amps. (3AG) |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 5 milliseconds typical |
| Mounting | Any position |
| Size | 3.27 inches wide, 5.65 inches high, 1.50 inches deep |
| Weight | 17 ounces |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |