The MPR-4 metering pulse register is designed to provide a totalized numerical value from 4 pulse inputs. Each input contains its own non-volatile counter, which is eight digits wide (99,999,999) which allows 100 million counts to be counted on each input before roll-over. The Pulse Value Register (PVR) displays the totalized value of all input pulses, that is, the number of input pulses for each input multiplied by each input's individual four digit multiplier value. The MPR-4 has four 3-wire ("K, Y & Z") inputs. The ten digit stored value along with the multiplier for each input may be viewed on a LCD display at any time without disturbing the operation of the unit. Typical applications include interfaces between utility metering devices and customer owned energy control systems, demand recorder applications, and supervisory control systems (SCADA) interfaces. The input pulse signal from the sending device to the MPR-4 is by four sets of "Y" & "Z" leads with a common "K" lead.
| Power Input | 120 to 277 VAC, burden 10 Ma |
| Input Signal | Four sets of 3-wire form "C" dry contacts. Sense voltage for all "K" leads is a common +5 VDC |
| Output | Display on LCD screen |
| Mounting | Normally in a vertical plane for ease of viewing |
| Size | 3.50 inches wide, 7.20 inches high, 1.50 inches deep |
| Weight | 13 ounces |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |