SPR-448
Quad Solid State Pulse Isolation Relay
GENERAL DESCRIPTION
The SPR-448 is an input/output termination unit designed specifically for the Landis + Gyr MaxSYS 2510 and Elite meters. It includes an integral 4-channel KYZ pulse isolation relay to protect the meter’s KYZ output board from transient voltages, induced electrical noise, over-currents (short-circuits), over-voltages and other conditions that might damage the meter. Metal oxide varistor (MOV) transient suppression is provided on each output. In addition, each output is equipped with a standard AGC/3AG style fuse that can be replaced by field personnel.
The input configuration of each input can be independently set on site as either a Form C (3-wire) or Form A (2-wire) input. The meter’s pulse output “J3” wire harness plugs directly into the DB-25 connector, allowing for quick and convenient connection. Screw terminals are provided for each output making field wiring a snap.
In addition to the isolation relays on the outputs, the SPR-448 features an 8-input termination section, providing a convenient way to interface external KYZ pulses or other digital inputs with the MaxSYS 2510 or Elite meters. Bright red LED’s have been added to display input status, allowing for easy and fast monitoring of all inputs.
The SPR-448 is mounted on an aluminum mounting plate with key-hole mounting slots, making it easy to mount the unit inside another enclosure. Additional mounting holes are provided in each corner of the mounting plate. The board is mounted approximately 9/16” above the mounting plate surface providing excellence isolation from ground. Transient suppression is provided on the power supply.
The SPR-448 is available in two versions: P/N SS5148A-00001 with perpendicular DB-25 connectors that are available from the front of the board, or P/N SS5148A-00002 with parallel DB-25 connectors that are available from the sides of the board.
Optional indoor (NEMA 1) and outdoor (NEMA 3R) enclosures are also available.
SPR-448 SPECIFICATIONS
ELECTRICAL
| Input |
120, 208 to 277 VAC. Burden: 10 mA at 120 VAC; 5 mA @ 240 VAC |
ISOLATION RELAY
| Signal Input |
Four independent field-selectable inputs. Form A or Form C inputs are provided by Landis + Gyr MaxSYS 2510 or Elite meters through the meter’s J3 DB-25 connector. Each input has “Yin” and “Zin” terminals wetted, pulled up with +13VDC. “Kin” terminal is the common return. The Form A input uses the “Yin” terminal, and the Form C input uses the “Yin” and “Zin” terminals for the input from the meter. |
| Output |
Four sets of dry contact Form C outputs (K,Y & Z) for energy pulses. K-Y or K-Z may be used for Form A pulses. The relay contacts are solid state with “no bounce” circuitry. Outputs are rated at 250VAC/VDC 1/10th Amp (100 milliamps). Factory fused at 1/10 amp @ 250 VAC with standard 3 AG (AGC) style fuses. |
| On-State Contact Resistance |
25 ohms maximum, 18 ohms typical |
| Insulation Resistance |
50 megohms typical |
| Operate and Release Time |
2 to 3 milliseconds typical |
| Input/Output Isolation Voltage |
3750V |
MECHANICAL
| Mounting |
Any position |
| Board Size |
5.5” Wide, 7.5” High, 1.25” Deep |
| Overall Assembly Size |
5.5” Wide x 9.0” High x 1.8” Deep |
| Weight |
12 ounces |
TEMPERATURE
| Temperature Range |
-38° C to +70° C, -36.4° F to +158° F |
| Humidity |
0 to 98% non-condensing |
ORDERING INFORMATION
| SS5148A-00001 |
With perpendicular "straight up" DB-25 connectors |
| SS5148A-00002 |
With parallel DB-25 connectors |