The TR-4C tone receiver is designed to receive tone transmissions from an SSI Model TT-4C tone transmitter. In normal operations, the TR-4C receives four sets of meter energy pulses in a three-wire Form C (K, Y, and Z) or 2-Wire Form A (K and Y) format. While the most common usage of the TR-4C is for energy pulses, it can receive any four Form A or Form C sets of contacts sent by the TT-4C tone transmitter. | Power Input | 120 VAC, 208-277 VAC Burden: 4 VA at 120VAC |
| Input Signal | DTMF tone signal from a TT-4C using a telephone leased line or a twisted wire pair should be between -40 dbm to +3 dbm. The input signal level may be adjusted by means of a variable resistor on the TR-4C. |
| Output | Four sets of dry “Form C” (K, Y, & Z) for energy pulses. The contacts are mercury-wetted “no-bounce” relays rated at 500VDC or 350VAC, 2 amps break, 5 amps carry. The maximum power rating of the contacts is 100VA. Factory fused at 1/2 amp. (3AG) |
| Contact Resistance | 50 milliohms maximum, 12 to 14 ohms typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 4 to 8 milliseconds typical |
| Mounting | Within 30 degrees of vertical. Mounted on aluminum base plate with mounting tabs |
| Size | 5.50 inches wide, 7.50 inches long, 2.00 inches high |
| Weight | 1.5 pounds |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | Contact Factory |