The CIR-2A customer interface relay is designed to provide two isolated "dry", mercury-wetted sets of contacts from a single Form "C" input. One set of contacts may be configured to either a Form "A" (K & Y) contact or a Form "C" (K, Y, & Z) contact. The second set of contacts is a 3-wire output typically used for a pulse recorder. The typical application is the utility's interface between the KWH meter & recorder, and a customer's energy control system. The CIR-2A provides in one compact ready-to-mount case everything necessary to provide a customer with energy control pulses in one box.
| Power Input | 90 to 325 VAC. Burden: 10 MA. at 120 VAC |
| Output | One set of "dry" Form "A" or Form "C" contacts (K & Y or K, Y, & Z) for selected by a user changeable switch located in the customer's compartment and one fixed set of Form "C" contacts located in the utility's compartment, both for energy pulses. The contacts are mercury- wetted "no bounce" relays rated at 500 VDC or 350 VAC 2 Amps. break, 5 amps carry. The maximum rating of the contacts is 100 VA. Factory fused at 1/2 amp. (3AG) |
| Sense Voltage | +13 VDC |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 2.5 milliseconds typical operate; 3.0 milliseconds typical release |
| Mounting | Within 30 degrees of vertical |
| Size | 9.00 inches wide, 11.00 inches high, 4.50 inches deep |
| Type/Material | NEMA 4X Fiberglass Enclosure |
| Weight | 9.5 pounds |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |