The CIR-3A customer interface relay is designed to provide two isolated sets of "dry" KWH mercury wetted contacts from a single Form "C" input, and a single end of DEMAND INTERVAL contact. One the KWH contact sets may be configured as either a Form "A" (K & Y) output or a Form "C" (K, Y, & Z) output. The second set of KWH contacts is a fixed 3-wire output typically used for a pulse recorder. The end of DEMAND INTERVAL output is a "dry" Form "A" contact. The typical application is the utility's interface between the KWH meter & recorder, and a customer's energy control system.
| Power Input | 90 to 325 VAC. Burden: 10 MA. at 120 VAC |
| Output | One set of "dry" Form "A" or Form "C" contacts (K & Y or K, Y, & Z) for selected by a user changeable switch located in the customer's compartment and one fixed set of Form "C" contacts located in the utility's compartment, both for energy pulses. A set of Form "A" contacts located in the user's compartment for end of demand interval timing. The contacts are mercury-wetted "no bounce" relays rated at 500 VDC or 350 VAC 2 Amps. break, 5 amps carry. The maximum rating of the contacts is 100 VA. Factory fused at 1/2 amp. (3AG) |
| Sense Voltage | +13 VDC |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 2.5 milliseconds typical operate; 3.0 milliseconds typical release |
| Mounting | Within 30 degrees of vertical |
| Size | 9.00 inches wide, 11.00 inches high, 4.50 inches deep |
| Type/Material | NEMA 4X Fiberglass Enclosure |
| Weight | 10 pounds |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |