The DPR-22 is a microcontroller-based dividing pulse relay designed to provide two sets of isolated "dry" 3-wire Form "C" contact (K, Y, & Z) from a field selectable 2-wire(Form A) or 3-wire(Form C) pulse input which has been divided by a user-selected number. The divider's ratio of input pulses to output pulses may be set anywhere between 1 to 255. Selection of the desired division ratio is by two small selector switches mounted on the relay's board and is easily field adjustable with a small screwdriver.
| Power Input | 90 to 325 VAC. Burden: 10 MA. at 120 VAC |
| Output | Two sets of "dry" Form "C" contacts (K, Y, & Z) for time or energy pulses. The contacts are mercury-wetted "no bounce" relays rated at 500 VDC or 350 VAC 2 Amps. break, 5 amps carry. The maximum rating of the contacts is 100 VA. Factory fused at 1/2 amp. (3AG) |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 2.5 milliseconds typical operate; 3.0 milliseconds typical release |
| Mounting | Within 30 degrees of vertical |
| Size | 3.50 inches wide, 7.20 inches high, 1.50 inches deep |
| Weight | 12 ounces |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |