The IPR-1 isolation pulse relay is designed to provide a single isolated "dry", mercury wetted form "C" (K, Y, & Z) output contact from a single form "C" energy pulse input and a single isolated "dry" mercury wetted form "A" or form "B" output contact for end of interval demand timing. Typical applications include interfaces between utility metering devices and customer owned energy control systems, demand recorder applications, and supervisory control systems (SCADA) interfaces. The IPR-1 relay is designed to retain the last valid energy pulse input status upon loss of the system's power thereby preventing false outputs from occurring. An incorrect sequence of input energy form "C" pulses will be detected and only the first valid pulse will result in an output. The timing pulse output closure for end-of-demand interval status may be field set, by means of a small switch, to either reproduce the original input timing pulse duration length or a short pulse closure (approximately 100 milliseconds)beginning at the start of the "end-of-demand-interval" input pulse.
| Power Input | 90 to 325 VAC. Burden: 10 MA. at 120 VAC |
| Output | One set of "dry" Form "C" contacts (K, Y, & Z) for energy and one set of "dry" Form "A" (or Form "B") contacts (K & Y ) for end- of- interval time pulses. The contacts are mercury-wetted "no bounce" relays rated at 500 VDC or 350 VAC 2 Amps. break, 5 amps carry. The maximum rating of the contacts is 100 VA. Factory fused at 1/2 amp. (3AG) |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 2.5 milliseconds typical operate; 3.0 milliseconds typical release |
| Mounting | Within 30 degrees of vertical |
| Size | 3.50 inches wide, 7.20 inches high, 1.50 inches deep |
| Weight | 15 ounces |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |