The LMR-1 load management relay provides three isolated "dry", mercury-wetted sets of contacts from a single Form "C" input. All three sets of contacts are configured as "Form C" (K, Y, & Z) contacts. The first set is available for the customer's use. The remaining two sets are designed for utility use. In addition, the LMR-1 has provisions for making utility control signals (end of interval, load control, etc.) conveniently accessible for customer use. The typical application of the LMR-1 is the utility's interface between the KWH meter & data or load profile recorders, and a customer-owned energy control system. The LMR-1 provides in one compact ready-to-mount case everything necessary to provide a customer with energy pulses and control signals in one box.
| Power Input | 90 to 325 VAC. Burden: 10 MA. at 120 VAC |
| Output | Three sets of "Form C" contacts (K, Y, & Z), one set located in the customer's compartment and two sets located in the utility's compartment. The contacts are mercury-wetted "no bounce" relays rated at 500 VDC or 350 VAC 2 Amps. break, 5 amps carry. The maximum rating of the contacts is 100 VA. Factory fused at 1/2 amp (3AG). |
| Sense Voltage | +13 VDC |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 2.5 milliseconds typical operate; 3.0 milliseconds typical release |
| Mounting | Within 30 degrees of vertical |
| Size | 9.00 inches wide, 11.00 inches high, 4.50 inches deep |
| Type/Material | NEMA 4X Fiberglass Enclosure |
| Weight | 9.5 pounds |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |