The RPR-1P repeating pulse relay is designed to provide a single isolated "dry", mercury-wetted form "C" (K, Y, & Z) contact from a single form "C" input where a sense voltage from other equipment is present. To prevent loading of the other equipment's sense voltage source, the other equipment's sense voltage should be higher than 14 VDC. The RPR-1P will also supply its own sense voltage when no other sense voltages are present. Typical applications include interfaces between utility metering devices and customer owned energy control systems, demand recorder applications, and supervisory control systems (SCADA) interfaces.
| Input | 90 to 325 VAC. Burden: 10 MA. at 120 VAC |
| Output | One set of "dry" form "C" contacts (K, Y & Z) for energy pulses. The mercury wetted "no bounce" relay contacts are rated at 500 VDC or 350 VAC 2 Amps. break, 5 amps carry. The maximum rating of the contacts is 100 VA. Factory fused at 1/2 amp. (3AG) |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 1 to 2 milliseconds typical |
| Mounting | Within 30 degrees of vertical |
| Size | 3.27 inches wide, 5.65 inches high, 1.50 inches deep |
| Weight | 12 ounces |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |