The RPR-2 repeating pulse relay is designed to provide isolation in the form of two sets of isolated "dry" (no voltage present), mercury wetted form "C" (K, Y, & Z) relay contacts from a single form "C" "dry" input over a wide voltage operating range. Typical applications include isolation interfaces between utility metering devices (KWH, KVAR, etc.) and customer owned energy control systems, demand recorder applications, and supervisory control systems (SCADA) interfaces. The RPR-2 relay is designed to retain the last received valid input status upon the loss of the system's power thereby preventing false outputs from occurring. An incorrect sequence of received input pulses is detected and only the first valid pulse will result in an output.
| Input | 85 to 325 VAC or VDC. Burden: 10 MA. at 120 VAC. |
| Output | Two sets of "dry" form "C" contacts (K, Y, & Z) for energy pulses. The contacts are mercury wetted "no bounce" relays rated at 500 VDC or 350 VAC 2 Amps. break, 5 amps carry. The maximum rating of the contacts are 100 VA. Factory fused at 1/2 amp. (3AG) |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 1 to 2 milliseconds typical |
| Mounting | Within 30 degrees of vertical |
| Size | 3.27 inches wide, 5.65 inches high, 1.50 inches deep |
| Weight | 8 ounces |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | Contact Factory |