The RPR-2P repeating pulse relay is designed to provide two isolated "dry", mercury-wetted form "C" (K, Y, & Z) contacts from a single form "C" input over a wide voltage range. The RPR-2P relay is identical to the RPR-2 with the exception that the RPR-2P has a built-in low voltage transformer isolated power supply. The sense voltage (Kin) to the data sending circuit (typically a meter) is 13 VDC instead of the higher line voltage used in the RPR-2 relay.
| Input | 90 to 325 VAC. Burden: 10 MA. at 120 VAC |
| Output | Two sets of "dry" form "C" contacts (K, Y, & Z) for energy pulses. The contacts are mercury wetted "no bounce" relays rated at 500 VDC or 350 VAC 2 Amps. break, 5 amps carry. The maximum rating of the contacts is 100 VA. Factory fused at 1/2 amp. (3AG) |
| Contact Resistance | 50 milliohms maximum, 12 to 14 typical |
| Insulation Resistance | 50 megohms typical |
| Operate and Release Time | 4 to 8 milliseconds typical |
| Mounting | Within 30 degrees of vertical |
| Size | 3.27 inches wide, 5.65 inches high, 1.50 inches deep |
| Weight | 12 ounces |
| Temperature Range | -38° C to +70° C, -36.4° F to +158° F |
| Humidity | 0 to 98% non-condensing |
| Input Voltages | 125 VDC input using the DCS-1 Power Supply. Contact factory for other input voltages. |