| Input |
120 to 277 VAC. Burden: 10 MA. at 120 VAC |
| Signal Input |
Four independent field-selectable inputs, Form A or Form C. Each input has "Yin" and "Zin" terminals wetted - pulled up with +13VDC. "Kin" terminal is the common return. The Form A input uses the "Yin" terminal; The Form C input uses the "Yin" and "Zin" terminals for the input from the meter. |
| Output |
Four sets of "dry" Form C contacts (K, Y, & Z) for energy pulses. The relay contacts are solid state with "no bounce" circuitry. Outputs are rated at 250VAC/VDC 1/10th Amp(100 milliamps). Factory fused at 1/10 amp @ 250VAC. (3AG) |
| Contact Resistance |
25 ohms maximum, 18 ohms typical |
| Insulation Resistance |
50 megohms typical |
| Operate and Release Time |
2 to 3 milliseconds typical |
| Input/Output Isolation Voltage |
3750V |